Special conditions for ATEX, flameproof enclosures
DANGER – Risk of explosion
Hot parts inside the housing may pose a risk of explosion.
Never open the device immediately after switch-off. Always wait at least four minutes before
opening the unit.
Prior to final installation, the owner must decide how the device is to be used, either
A) as a device featuring the "Ex i" type of ignition protection, or
B) as a device with the "Ex d" type of ignition protection,
and he/she must mark the selected type of use on the name plate in a permanent manner.
Specific ambient conditions such as chemical corrosion should be taken into account when
affixing the permanent mark. Only the manufacturer may change the selected type of use
following a review.
Variants that also meet the requirements for the "intrinsically safe" type of ignition protection
may not be used as "intrinsically safe", if they have been previously used as a flameproof
type of ignition protection.
Manipulation of the device by the user is not permitted. Modifications to the device may only
be performed by the manufacturer or an explosion protection specialist.
The splash guard cap must be screwed in place to achieve the IP 65 / NEMA 4x protection
class. Operating the devices without the splash guard cap is prohibited.
The device may only be supplied with instrument air that is free of oil, water, and dust. Do
not use flammable gases, oxygen, or oxygen-enriched gas.
Secure the cable and line entries against twisting and becoming loose by applying adhesive
of medium strength.
In the event of high torsional forces, the bearing sleeves on the shaft for the position pickoff
must be replaced due to wear (significant system deviation).
If the positioner is used at an ambient temperature above 60 °C (140 °F) or below -20 °C (-4
°F), use cable entries and lines approved for a service temperature corresponding to the
maximum ambient temperature increased by 10 K or corresponding to the minimum ambient
temperature, respectively.
NOTICE – Potential damage to parts
If the sealing surface is damaged, the "Ex d" explosion protection is no longer guaranteed.
Handle the housing cover carefully. Place the housing cover only on a smooth and clean
surface.
DANGER – Risk of explosion (only applies to TZIDC-200)
It is prohibited to use the local communication interface (LKS) in an explosion risk area.
Never use the local communication interface (LKS) on the main board with a positioner that is
being used in an explosion risk area.