Options; Accessories - ABB TZIDC-200 Operating Instructions Manual

Electro-pneumatic positioner. for 4 ... 20 ma two-wire technology, hart, profibus pa, foundation fieldbus
Hide thumbs Also See for TZIDC-200:
Table of Contents

Advertisement

9.3.9

Options

Module for the emergency shutdown function
Supply voltage
Safe position is activated when
Explosion protection
Without the separate 24 V DC feed, the positioner moves into safe
position independent of the processor by depressurizing the actuator.
In addition, the feed for the I/P module is isolated via an optocoupler.
Communication and feedback remain active because the positioner is
fed via a bus line. The shutdown switching input is electrically isolated
from the setpoint signal.
The emergency shutdown function can save use of additional
solenoid valves and has a safety certificate from TÜV Rheinland acc.
to AK4. The plug-in module also has an Ex certificate for use in
intrinsically safe circuits.
Mechanical position indicator
-
Indicator disk
-
Cover with transparent dome
-
Symbol label
-
Extension shaft
Digital position feedback with proximity switches
Two proximity switches for independent position signaling. Switching
points adjustable between 0 ... 100%
Current circuits acc. to DIN 19234 / NAMUR
Supply voltage
Signal current < 1.0 mA
Signal current > 2.0 mA
(function dependent on software and electronics for actuator)
Direction of action (logical state)
Proximity switch
< Lim. 1
SJ2-SN (NC)
0
SJ2-S1N (NO)
1
Digital position feedback with 24 V microswitches
Two microswitches for independent position signaling. Switching
points adjustable between 0 ... 100 %.
Voltage
Load rating
Contact surface
Change from one to two columns
42/18-85-EN
24 V DC (20 ... 30 V DC)
(electrically isolated from input
signal)
Voltage < 5 V
Ex ia IIC
5 ... 11 V DC
Switching state logical "0"
Switching state logical "1"
Position
> Lim. 1
< Lim. 2
> Lim. 2
1
1
0
0
0
1
*
max. 24 V AC / DC
max. 2 A
10 µm Gold (AU)
TZIDC-200, TZIDC-210, TZIDC-220
Mechanical position indicator
Indicator disk in enclosure cover, linked with positioner feedback shaft
through magnetic coupling.
*
The "digital feedback" is activated directly from the axis of rotation for
the variable pick-off and can only be used with the "mechanical
position indicator".
IMPORTANT (NOTE)
These options are also available for retrofitting by Service.

9.3.10 Accessories

Mounting material
-
Attachment kit for linear actuators to DIN / IEC 534 / NAMUR
-
Attachment kit for part-turn actuators to VDI / VDE 3845
-
Attachment kit for integral mounting to control valves
-
Attachment kit for actuator-specific attachment upon request
Pressure gauge block
-
Pressure gauges for supply and output pressure
-
Pressure gauges with housing ø 28 mm
-
Aluminum connection block in black
-
Installation material for mounting on positioner
Filter regulator
All metal version in brass, varnished black, bronze filter element
(40 µm) and condensate drain.
Max. pre-pressure 16 bar (232 psi), output adjustable to 1.4 ... 6 bar
(20 ... 90 psi)
Specifications