Ex relevant specifications
10.3.3.2 Operation as intrinsically safe equipment
Designation:
Certificate No.:
Issue No.:
Type:
Standards:
Temperature class
T4
T6
1)
1)
When using the "digital feedback" plug-in module in temperature class T6, the maximum
permissible ambient temperature range is -40 ... 35 °C (-40 ... 95 °F).
Change from one to two columns
IECEx certification conditions, operation as intrinsically safe equipment
Special conditions relevant to the safe use of intrinsically safe positioners:
The local communication interface (LKS) for the TZIDC and the TZIDC-200 may only be
operated at U
Special conditions for the safe use of positioners, labeled Ex nA II T6 or Ex nL IIC T6:
Only connect devices to circuits in zone 2, which are suitable for use in potentially explosive
atmospheres, zone 2, and the prevailing conditions at the installation site.
It is only permissible to connect, disconnect, and switch live circuits when carrying out
installation, maintenance, or repair tasks.
Note: It is considered to be unlikely that a potentially explosive atmosphere would be present at
the same time that installation, maintenance, or repair work was being carried out.
For the "mechanical digital feedback" circuit, external measures must be taken to prevent the
rated voltage from being exceeded by more than 40 % in the event of transient disturbances..
Only use non-flammable gases as pneumatic auxiliary energy.
Only use suitable cable entries which meet the requirements of IEC 60079-15.
Change from one to two columns
Change from one to two columns
64
Ex ia IIC T6 resp. T4 Gb
IECEx TUN 04.0015X
5
TZIDC-220
IEC 60079-0:2011
IEC 60079-11:2011
Ambient temperature range
-40 ... 85 °C
-40 ... 40 °C
≤ 30 V DC outside the potentially explosive area.
m
TZIDC-200, TZIDC-210, TZIDC-220
Electrical TZIDC-220 data for ia/ib/ic for groups IIB/IIC
Signal circuit
(Terminal +11 / -12 or + / -)
The following plug-in modules can be used as an option:
With the intrinsically safe Ex i IIC type of
ignition protection, only for connection to a
certified intrinsically safe circuit with max.
values:
Plug-in module for
U
= 30 V
i
shutdown contact
l
= 320 mA
i
input
P
= 1.1 W
i
(Terminal +51 / -52
C
= 3.7 nF
i
or +85 / -86)
L
negligibly small
i
With the intrinsically safe Ex i IIC
type of ignition protection, only for
connection to a certified FISCO
power supply unit or a barrier, i.e.,
a power supply unit with
maximum values according to the
following table:
Voltage = 24 V
Current = 250 mA
Output = 1.2 W
Characteristic curve = linear
42/18-85-EN