Technical data

What this chapter contains

This chapter contains the technical specifications of the inverter unit, for example, the
ratings, technical specifications and requirements, and provisions for fulfilling the
requirements for CE and other markings.

Ratings

Inverter unit
type
Frame
size
ACS880-107-
...
U
= 400 V
N
004A8-3
R1i
006A0-3
R1i
008A0-3
R1i
0011A-3
R2i
0014A-3
R2i
0018A-3
R2i
0025A-3
R3i
0035A-3
R3i
0044A-3
R3i
0050A-3
R3i
0061A-3
R4i
0078A-3
R4i
0094A-3
R4i
0100A-3
R4i
0140A-3
R6i
0170A-3
R6i
0210A-3
R6i
0250A-3
R6i
Input
ratings
No-overload use
I
I
I
1
max
N
A
A
A
5.8
7.0
4.8
7.2
8.8
6.0
9.6
10.5
8.0
12.6
13.5
10.5
16.8
16.5
14.0
21.6
21
18.0
30
33
25
42
44
35
53
53
44
60
66
50
73
78
61
94
100
78
113
124
94
125
125
104
169
183
141
203
220
169
247
268
206
295
320
246
Output ratings
Light-overload
P
S
I
N
N
Ld
kW
kVA
A
1.5
3.3
4.5
2.2
4.2
5.5
3.0
5.5
7.6
4.0
7.3
9.7
5.5
9.7
13.0
7.5
12.5
16.8
11.0
17.3
23
15.0
24.2
32
18.5
30.5
41
22
35
46
30
42
57
37
54
74
45
65
90
55
72
100
75
98
135
90
117
162
110
143
198
132
170
236
Technical data 133
8
Heavy-duty
use
use
P
I
P
Ld
Hd
kW
A
kW
1.5
4.0
1.5
2.2
5.0
1.5
3.0
6.0
2.2
4.0
9.0
3.0
5.5
11.0
4.0
7.5
14.0
5.5
11.0
19.0
7.5
15.0
29
11.0
18.5
35
15.0
22
44
30
52
37
69
45
75
55
78
75
105
90
126
110
154
132
184
Hd
22
22
30
37
37
55
55
75
90