142 Technical data

Input power (DC) connection

Voltage (U
)
1
Drive AC supply network
type

Motor (AC) connection

Motor types
Voltage (U
)
2
Frequency (f
)
2
Current
Switching frequency
Maximum recommended
motor cable length
ACS880-107-xxxxx-3: 513...566 V DC. This is indicated in the type
designation label as typical input voltage level (566 V DC).
ACS880-107-xxxxx-5: 513...707 V DC. This is indicated in the type
designation label as typical input voltage levels (566/679/707 V DC).
ACS880-107-xxxxx-7: 709...976 V DC. This is indicated in the type
designation label as typical input voltage levels (742/849/976 V DC).
TN (grounded) and IT (ungrounded) systems, corner-grounded systems up
to 600 V AC
Asynchronous AC induction motors, permanent magnet synchronous motors
and AC induction servomotors
3-phase symmetrical, U
ACS880-107-xxxxx-3: 0...400 V AC. The maximum value (400 V) is a typical
drive input voltage level shown on the type designation label of the supply
unit corresponding to 380...415 V AC.
ACS880-107-xxxxx-5: 0...400/480/500 V AC. The maximum values
(400/480/500 V) are typical drive input voltage levels shown on the type
designation label of the supply unit corresponding to 380...500 V AC.
ACS880-107-xxxxx-7: 0...525/600/690 V AC. The maximum values
(525/600/690 V) are typical drive input voltage levels shown on the type
designation label of the supply unit corresponding to 525...690 V AC.
0...500 Hz, except
0...120 Hz with sine output filters (option +E206)
0...120 Hz for frames R1i...R5i with du/dt filters (option +E205)
0...200 Hz for frames R6i and R7i with du/dt filters (option +E205)
• For higher operational output frequencies, please contact your local ABB
representative.
• Operation above 150 Hz may require type-specific derating. For more
information, contact your local ABB representative.
See section
Ratings
(page 133).
Frames R1i...R4i: 4.5 kHz (typical)
Frames R5i...R8i: 3 kHz (typical)
The switching frequency can vary per frame and voltage. For exact values,
please contact your local ABB representative.
Frames R1i...R2i: 150 m (492 ft)
Frames R3i...R7i: 300 m (984 ft)
Note: Tested with 100 m (328 ft) for EMC Category C3. See standards and
markings information in Electrical planning instructions for ACS880
multidrive cabinets and modules (3AUA0000102324 [English]).
Frame R8i and multiples: 500 m (1640 ft)
at field weakening point:
max