102 Start-up

Checks with voltage connected to inverter unit

The table below contains the basic checks on the inverter unit when voltage is connected
to it.
Action
Complete the pending ID (motor identification) run.
WARNING! Make sure the motor can be started and
rotated as required by the selected ID run mode
(parameter 99.13 ID run requested).
Check the rotation direction of the motor.
Check the operation of the pulse encoder (if present).
Check the functioning of the emergency stop function from each
operating location.
Validate the Safe torque off function.
WARNING! The safety functions cannot be
considered safe until they are validated.
Validate the safety functions (+Q973, if present) according to the
procedure described in FSO-12 user's manual.
WARNING! The safety functions cannot be
considered safe until they are validated.
Validate any other safety functions (Emergency stop, Prevention of
unexpected start-up, etc.) according to the procedures described
in their respective manuals.
WARNING! The safety functions cannot be
considered safe until they are validated.
Information
Refer to the Firmware manual of the
inverter control program.
Refer to the user manual of the pulse
encoder interface module.
Refer to chapter
The Safe torque off
function, section
Start-up including
acceptance test
(page 164).
Refer to FSO-12 safety functions
module User's manual
(3AXD50000015612 [English]).