The GSD (Geräte-Stamm-Datei) is online available in the following language versions.
Further language versions are available on inquires:
Name
SPEEDBUS.GSD
SPEEDBUS.GSG
SPEEDBUS.GSE
The GSD files may be found at www.vipa.com at the service area.
The integration of the SPEEDBUS.GSD takes place with the following proceeding:
1.
Go to the service area of www.vipa.com.
2.
Load from the download area at 'Config files è PROFIBUS' the according file for
your System 300S.
3.
Extract the file to your work directory.
4.
Start the hardware configurator from Siemens.
5.
Close every project.
6.
Select 'Options è Install new GSD-file'.
7.
Navigate to the directory VIPA_System_300S and select SPEEDBUS.GSD an.
ð The SPEED7 CPUs and modules of the System 300S from VIPA may now be
found in the hardware catalog at PROFIBUS-DP / Additional field devices / I/O /
VIPA_SPEEDBUS.
The embedding of the CPU 317-4PN23 happens by means of a virtual PROFIBUS
master system with the following approach:
1.
Perform a hardware configuration for the CPU
tion - CPU' on page 47
2.
Configure always as last module a Siemens DP master CP 342-5 (342-5DA02
V5.0). Connect and parameterize it at operation mode "DP-Master".
3.
Connect the slave system "VIPA_SPEEDbus". After installing the SPEEDBUS.GSD
this may be found in the hardware catalog at PROFIBUS DP / Additional field
devices / I/O / VIPA / VIPA_SPEEDBUS.
4.
For the slave system set the PROFIBUS address 100.
5.
Configure at slot 0 the VIPA CPU 317-4PN23 of the hardware catalog from
VIPA_SPEEDbus.
6.
By double clicking the placed CPU 317-4PN23 the properties dialog of the CPU
may be opened.
As soon as the project is transferred together with the PLC user program to the CPU, the
parameters will be taken after start-up.
The hardware configuration, which is shown here, is only required, if you
want to customize the VIPA specific parameters.