VIPA System 300S
Installation of the
SPEEDBUS.GSD
Proceeding
HB140 | CPU | 317-4PN23 | en | 18-01
The GSD (Geräte-Stamm-Datei) is online available in the following language versions.
Further language versions are available on inquires:
Name
SPEEDBUS.GSD
SPEEDBUS.GSG
SPEEDBUS.GSE
The GSD files may be found at www.vipa.com at the service area.
The integration of the SPEEDBUS.GSD takes place with the following proceeding:
1.
Go to the service area of www.vipa.com.
2.
Load from the download area at 'Config files è PROFIBUS' the according file for
your System 300S.
3.
Extract the file to your work directory.
4.
Start the hardware configurator from Siemens.
5.
Close every project.
6.
Select 'Options è Install new GSD-file'.
7.
Navigate to the directory VIPA_System_300S and select SPEEDBUS.GSD an.
ð The SPEED7 CPUs and modules of the System 300S from VIPA may now be
found in the hardware catalog at PROFIBUS-DP / Additional field devices / I/O /
VIPA_SPEEDBUS.
Thus, the VIPA components can be displayed, you have to deactivate the
"Filter" of the hardware catalog.
The embedding of the CPU 317-4PN23 happens by means of a virtual PROFIBUS
master system with the following approach:
1.
Start the Siemens TIA Portal.
2.
Configure in the Device configuration the according Siemens CPU.
3.
Configure your System 300 modules.
4.
Configure your Ethernet PG/OP channel always as last module after the really
plugged modules.
5.
Configure always as last module a Siemens DP master CP 342-5 (342-5DA02
V5.0). Connect and parameterize it at operation mode "DP-Master".
Configuration with TIA Portal
TIA Portal - Setting VIPA specific CPU parameters
Language
German (default)
German
English