VIPA System 300S
Take IP address parame-
ters in project
HB140 | CPU | 317-4PN23 | en | 18-01
7.
Confirm with [Assign IP configuration].
ð Directly after the assignment the Ethernet PG/OP channel is online reachable
using the set IP address data. The value remains as long as it is reassigned, it
is overwritten by a hardware configuration or an factory reset is executed.
Due to the system you may get a message that the IP address could not
be assigned. This message can be ignored.
1.
Open your project.
2.
If not already done, configure in the 'Device configuration' a Siemens CPU 317-2
PN/DP (6ES7 317-2EK14-0AB0 V3.2).
3.
Configure the System 300 modules.
4.
For the Ethernet PG/OP channel you have to configure a Siemens CP 343-1 (6GK7
343-1EX11 0XE0) always as last module after the really plugged modules.
5.
Open the "Property" dialog by clicking on the CP 343-1EX11 and enter for the CP at
"Properties" at "Ethernet address" the IP address data, which you have assigned
before.
6.
Transfer your project.
TIA Portal - Hardware configuration - Ethernet PG/OP channel
Configuration with TIA Portal
155