Operation; Menu Survey - Danfoss EKC 347 Instructions Manual

Hide thumbs Also See for EKC 347:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 8

Operation

Display
The values will be shown with three digits, and after an opera-
tion the controller will return to its standard mode and show the
measured liquid level.
Light-emitting diodes (LED) on front panel
There are LED's on the front panel which will light up when the
corresponding relay is activated.
The upper LED will indicate the valve's opening degree. A short
pulse indicates a slow liquid flow and a long pulse a fast liquid
flow.
The three lowest LED's will flash, if there is an error in the regula-
tion.
In this situation you can upload the error code on the display and
cancel the alarm by giving the uppermost button a brief push.
The buttons
When you want to change a setting, the two buttons will give you
a higher or lower value depending on the button you are push-
ing. But before you change the value, you must have access to the
menu. You obtain this by pushing the upper button for a couple
of seconds - you will then enter the column with parameter codes.
Find the parameter code you want to change and push the two
buttons simultaneously. When you have changed the value, save
the new value by once more pushing the two buttons simultane-
ously.
Gives access to the menu (or cuts out an alarm)
Gives access to changes
Saves a change
Examples of operations
Set reference
1. Push the two buttons simultaneously
2. Push one of the buttons and select the new value
3. Push both buttons again to conclude the setting
Set one of the other menus
1. Push the upper button until a parameter is shown
2. Push one of the buttons and find the parameter you want to
change
3. Push both buttons simultaneously until the parameter value is
shown
4. Push one of the buttons and select the new value
5. Push both buttons again to conclude the setting
Literature survey:
Manual for EKC 347 ..............................................................RS8AX---
Instruction for EKC 347 .......................................................RI8BY---
Installation guide, "Data communication link
for ADAP-KOOL® " .................................................................RC8AC---
8
ENGLISH
Instructions RI8BY553 DKRCC.PI.RP0.A1.ML / 520H4018 © Danfoss 01/2011

Menu survey

Function
Normal display
Read the measured liquid level
If you wish to see the actual opening degree, give the
lower button a brief push
If you wish to set the required setpoint you obtain ac-
cess by pushing both buttons simultaneously
Level control
External contribution to the reference. Cf. also o10.
Value is set in %-points.
Start / stop of level control
Alarm
Upper level limit
Lower level limit
Time delay for upper level limit
Time delay for lower level limit
Level alarm limit
Delay for level alarm
The level alarm is linked to:
0: Rising level (higher level than A16)
1: Falling level (lower level than A16)
2: Same function as if A18=0. When A2 alarm is gener-
ated and Relay for lower level limit, gives OFF signal
(cut out).
3: Same function as if A18=1 When A2 alarm is gener-
ated and Relay for lower level limit, gives OFF signal
(cut out).
Function for Alarm relay when A1, A2 or A3 alarms are
detected.
0: Alarm relay to be activated when A1 or A2 or A3 are
detected.
1: Alarm relay only to be activated when A3 is detected.
Regulating parameters
P - band
I: Integration time Tn
Period time (only if AKV/A valve is used)
Max. opening degree
Min. opening degree
Neutral zone (only for ICM valve)
Definition of regulating principle
Low: On the low-pressure side (valve closes when
liquid level is rising)
High: On the high-pressure side (valve opens when
liquid level is rising)
Miscellaneous
Controller's address
ON/OFF switch (service-pin message)
Define valve and output signal:
1: ICM. AO: 4-20 mA
2: ICM. AO: 0-20 mA
3: AKV/A, AO: 4-20 mA
4: AKV/A, AO: 0-20 mA
Or if a master/slave function is used:
5: AKV/A, MASTER
6: AKV/A, SLAVE 1/1. AO:4-20 mA
7: AKV/A, SLAVE 1/1. AO:0-20 mA
8: AKV/A, SLAVE 1/2. AO:4-20 mA
9: AKV/A, SLAVE 1/2. AO:0-20 mA
10: AKV/A, SLAVE 2/2. AO:4-20 mA
11: AKV/A, SLAVE 2/2. AO:0-20 mA
12: AKV/A, SLAVE 1/1. AO:4-20 mA - AO always updated
13: AKV/A, SLAVE 1/1. AO:0-20 mA- AO always updated
14: AKV/A, SLAVE 1/2. AO:4-20 mA- AO always updated
15: AKV/A, SLAVE 1/2. AO:0-20 mA- AO always updated
16: AKV/A, SLAVE 2/2. AO:4-20 mA- AO always updated
17: AKV/A, SLAVE 2/2. AO:0-20 mA- AO always updated
SW = 1.1x
Pa-
Fac.
ram-
Min.
Max.
set-
eter
ting
-
% 50.0
-
% 0
-
0%
100%
100
r06
-100
100
0.0
r12
OFF/0 ON/1
1
A01
0 %
100%
85
A02
0%
100%
15
A03
0 s
999 s
50
A15
0 s
999 s
10
A16
0%
100%
20
A17
0 s
999 s
0
A18
0
3
0
A19
0
1
0
n04
0%/Off 200%
30
600/
n05
60
400
Off
n13
3 s
10 s
6
n32
0%
100%
100
n33
0%
100%
0
n34
2%
25%
2
n35
Low/0 Hig/1
0
o03* 0
60
0
o04* OFF
ON
o09
1
17
1
EKC 347