Connection of the ironer evacuation system

Fresh air inlet

To allow the dryer ironer to work at its
best, it is important that the laundry air
inlet passes through an opening from the
outside.
The fresh air arrival must be equivalent to
the volume of evacuated air (please refer
to the output of the fans at zero pressure in
the technical characteristics).
Note : In the case of several machines,
these values should be added together.
In order to prevent drafts in the room, the
best solution is to place the air inlet behind
the machine.
In the case of a machine with gas heating,
it is essential that the rooms should be
ventilated.
The free section of the air inlet must be
5 times greater than the section of the
evacuation pipe.
Do not forget to allow for the fact that grills
often occupy half the total area of the free
air opening.

Evacuation duct

It is recommended that a separate smooth-walled evacuation duct should be connected to
each dryer, providing the least possible resistance to air.
Check that the shaft fl ow is at least twice the capacity of the ironer exhaust fan.
04102011/GB
51.2010
To prevent any risk of burning, the vapours' evacuation duct of the
fl atwork ironers of the linen has to be temperature insulated (to be
done by the customer).
It is essential that the diameter of the evacuation pipe should be
selected as a function of each installation so that the pressure
loss never exceed 200 Pa = 0.029 psi (value measured at ambient
temperature).
These conditions are ABSOLUTELY ESSENTIAL for correct working of
the ironer.