Write_Read_Data / Data_Exchange (Default_Sap) - Profichip VPC3+S User Manual

Hide thumbs Also See for VPC3+S:
Table of Contents

Advertisement

6 PROFIBUS DP Extensions
Address
0DH
Figure 6-10: Coding of New_Diag_Cmd
Byte
0
1
2
3
4
5
6
:
n
Figure 6-11: Format of the Diagnosis-Buffer
The Ext_Diag_Data must be entered into the buffers after the VPC3+S
internal diagnosis data. Three different formats are possible here: device-
related, ID-related and port-related. If PROFIBUS DP extensions shall be
used, the device-related diagnosis is substituted by alarm and status
messages. In addition to the Ext_Diag_Data, the buffer length also includes
the VPC3+S diagnosis bytes (R_Len_Diag_Buf 1, R_Len_Diag_Buf 2).
6.2.5

Write_Read_Data / Data_Exchange (Default_SAP)

Writing Outputs
The VPC3+S writes the received output data in the 'D' buffer. After an error-
free receipt, the VPC3+S shifts the newly filled buffer from 'D' to 'N'. In
addition, the DX_Out interrupt is generated. The user now fetches the
current output data from 'N'. The buffer changes from 'N' to 'U' with the
Next_Dout_Buffer_Cmd, so that the current data can be transmitted to the
application by a RD_Output request from a DP-Master.
52
Bit Position
7
6
5
4
0
0
0
0
Bit Position
7
6
5
4
user input
Revision 1.04
3
2
1
0
0
0
0
0
0
1
1
0
3
2
1
0
VPC3+S User Manual
Copyright © profichip GmbH, 2012
Designation
New_Diag_
Buffer_Cmd
No_Buffer
Diag_Buf1
Diag_Buf2
Designation
Ext_Diag_Data
(n = max. 243)