Parameters 2845 "Max. f/P" and 2846 "Min. f/P" are shared between fixed var and fixed voltage
because they both use the same analogue input.

4.8.3 External set point selection

There are various principles for the GPC to control the genset through set point selection. These are internal
or external set points or optional control via external communication.
Set points via external communication is optional; Modbus (H2) or Profibus (H3).