Rmi Water - Deif GPC-3 Designers Reference Handbook

Generator paralleling controller
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

GPC-3 DRH 4189340587 UK
Pressure
Bar
psi
0
0
0.5
7
1.0
15
1.5
22
2.0
29
2.5
36
3.0
44
3.5
51
4.0
58
4.5
65
5.0
73
6.0
87
7.0
102
8.0
116
9.0
131
10.0
145
The configurable type is configurable with eight points in the range 0 to 480 Ω. The resistance
as well as the pressure can be adjusted.
If the RMI input is used as a level switch, then be aware that voltage must not be connected to
the input. If any voltage is applied to the RMI input, it will be damaged. Refer to the Application
Notes for further wiring information.

4.6.6 RMI water

This RMI input is used to measure the cooling water temperature.
DEIF A/S
RMI sensor type
Type 1
Type 2
Ω
Ω
10.0
10.0
27.2
44.9
31.3
62.9
81.0
51.5
99.2
117.1
71.0
134.7
151.9
89.6
168.3
184.0
107.3
124.3
140.4
155.7
170.2
184.0
Additional functions
Type 3
Ω
Type 3 is not available when RMI
oil is selected
Page 44 of 122