3.11 Running mode description

3.11.1 Running mode description
Local mode
In local mode, the sequences must be activated with the display push-buttons, and all external commands
are ignored.
The following sequences can be activated in local mode:
Command Description
Close GB
The unit will synchronise and close the generator breaker. If the busbar is black, the unit will
close the GB directly (no sync.)
Open GB
The unit will de-load and open the generator breaker at the breaker open point
Remote mode
In remote mode, the command push-buttons are ignored and the sequences must be activated with com-
mands given in two ways:
1. Digital inputs are used
2. Modbus/Profibus commands are used
Fixed mode
In parameter 6141, it is possible to select between the following three settings: OFF (default), LOCAL or OFF.
If this parameter is set to either LOCAL or REMOTE, the unit will be locked into this mode. If the user tries to
change mode via an input or from the display, the following message will appear in the display: "Mode selec-
tion blocked".
It is also possible to lock the unit into a specific mode from M-Logic. Refer to the document "ML-2 application
notes M-Logic".
The standard GPC-3 is equipped with a limited number of digital inputs; refer to the installation
instructions and the data sheet for additional information about availability.

3.12 Password

Password level
The unit includes three password levels. All levels can be adjusted in the PC software.
Available password levels:
Password level
Customer
Service
Master
A parameter cannot be entered with a password that is ranking too low. But the settings can be displayed
without password entry.
DEIF A/S
Factory setting
2000
2001
2002
Access
Customer
Service
X
X
Functional descriptions
Master
X
X
X