Siemens SENTRON Manual page 107

Transfer switching equipment and load transfer switches
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

Note
In the case of the 3KC8 transfer switching equipment, the inputs for the power supply are
located on the electronic module. These are described in the section titled Inputs for voltage
measurement and power supply (Page 115).
On the one hand, the motor operator is supplied with power via its inputs (3KC4 only), and
on the other, remotely operated transfer switching is enabled via these inputs.
Designation
Pin
Power supply
301
(3KC4 only)
302
Control inputs of
312
the motor opera-
tor
313
314
315
316
317
NOTICE
Damage to the device
Do not connect inputs 312 to 317 to the power supply.
Manual, 08/2017, L1V30368969104A-02
Meaning
Explanation
-
Power supply
-
Power supply
Enable Ctrl
Remote mode enabled (if closed
with 317)
OFF
Priority command for the OFF
position (if closed with input 317)
II
Command for transfer to position II
(if closed with input 317)
I
Command for transfer to position I
(if closed with input 317)
O
Command for transfer to position O
(if closed with input 317)
C
Common control terminal for inputs
312-316
7.2 Functions of the inputs and outputs
Properties
208 – 277 V AC
± 20%;
45 ... 65 Hz
Use only with
floating contacts
and supply via
pin 317
Maximum cable
length: 100 m
Operation
Recommended
cable cross-
section
1.5 - 2.5 mm
2
1.5 - 2.5 mm
2
107

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3kc83kc4

Table of Contents