Siemens SENTRON Manual page 135

Transfer switching equipment and load transfer switches
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

Note
Defined timer settings for network / generator applications
When switching from the main source to the generator, an additional delay of 5 s is set after
the generator has become available. This can be disabled with pin 414.
After return transfer to the main source, a generator cooling time is fixed at 3 mins
(command to generator remains active).
The table contains a summary of the possible potentiometer settings:
Item
0
1
no.
Un
Auto
220 /
Conf
127
V
Freq.
ΔU /
-
5 /
ΔF
3 %
Trans-
-
0
fer
Delay/
Sec.
Return
-
0
Delay/
Min.
Note
The "Ready" LED starts to flash green as soon as settings are made on the potentiometers.
Manual, 08/2017, L1V30368969104A-02
7.4 Automatic mode - programming of the electronic module (3KC8 only)
2
3
4
5
380 /
400 /
415 /
480 /
220
230
240
277
V
V
V
V
50 Hz
6 /
7 /
8 /
9 /
3 %
4 %
4 %
5 %
1
2
3
4
1
2
3
4
6
7
8
9
208 /
220 /
230 /
240 /
120
127
132
138
V
V
V
V
10 /
11 /
12 /
13 /
5 %
6 %
6 %
7 %
5
8
10
15
5
8
10
15
10
11
12
380 /
400 /
415 /
220
230
240
V
V
V
60 Hz
14 /
15 /
16 /
7 %
8 %
8 %
20
30
40
20
30
40
Operation
13
14
480 /
-
277
V
18 /
20 /
9 %
10 %
50
60
50
60
135