Circuit Diagram For The 3Kc8 Transfer Switching Equipment - 3-Pole Transfer Switching Equipment - Siemens SENTRON Manual

Transfer switching equipment and load transfer switches
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

Connection
6.1 Network types
6.1.2.3
Circuit diagram for the 3KC8 transfer switching equipment - 3-pole transfer switching
equipment
Figure 6-5
F1
F2
With this arrangement there is no neutral conductor available. For this reason, the following
optional accessories can/must be used for establishing this network:
● 2 x autotransformer 3KC9824-1. For information, see the section titled Installing and
connecting an autotransformer (400 V / 230 V) (Page 79).
● The auxiliary conductor terminal kit is required in the case of the 3-pole variant for
connecting the electronic module, and it must be mounted before connection to the
source. See the section titled Connecting the auxiliary conductor terminal 3KC9822-,
3KC9832- for a three-phase 3-wire network (3-pole) (Page 95).
The dual power supply (DPS) accessory is not required with the 3KC8 transfer switching
equipment since it is supplied with power via two inputs of the electronic module.
36
Three-phase 3-wire network without neutral for the 3KC8 transfer switching equipment
(3-pole)
2 x 3NW6002-1
1 x 3NW7023
1 x 3NW6004-1
1 x 3NW7013
2 A, gG
4 A, gG
Manual, 08/2017, L1V30368969104A-02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3kc83kc4

Table of Contents