Siemens SENTRON Manual page 187

Transfer switching equipment and load transfer switches
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

Short-circuit behavior
Short-circuit current ratings in compliance with IEC 60947-6-1
Short-time withstand current
I
(
, 60 ms, 415 V)
cw
Short-circuit current making
capacity
I
(
, 415 V)
cm
Short-circuit current ratings in compliance with IEC 60947-3
Short-time withstand current
I
(
, 60 ms, 415 V)
cw
Short-circuit current making
capacity
I
(
, 415 V)
cm
Conditional short-circuit current with fuse
Continuous current of upstream
fuse
Conditional short-circuit current
with fuse (690 V) IEC 60947-3
Conditional short-circuit current
with fuse (415 V) IEC 60947-6-1
Let-through current of gG fuse at
415 V; max. permissible
I
t value of the gG fuse at
2
400/500 V; max. permissible
Transfer switching properties
Switching time I-0 & II-0 RTSE /
ATSE
Switch-off time I-0-II & II-0-I
IEC 60947-6-1
Transfer time I-0-II & II-0-I
IEC 60947-6-1
Transfer time I-0-II & II-0-I
IEC 60947-6-1 with source monitor-
ing
Motor operator rated apparent pow-
er at 230 V AC
Motor operator peak inrush current
at 230 V AC
Manual, 08/2017, L1V30368969104A-02
11.2 Technical specifications 3KC4 and 3KC8 from 1250 A to 3200 A
3KC4.52
3KC4.54
3KC8.52
3KC8.54
kA
25
kA
52.5
kA
35
kA
73.5
A
1250
2 x 800
kA
100
kA
100
kA
100
kA
s
--
2
s
1.4
s
1.4
s
2.8
s
3.1
VA
184
A
2
3KC4.56
3KC8.56
32
50
67.2
105
50
50
105
105
--
100
--
100
--
100
--
--
--
1.4
1.6
1.5
1.2
2.9
2.8
3.3
2.8
230
322
2
3.5
Technical specifications
3KC4.58
3KC4.60
3KC8.58
3KC8.60
50
50
105
105
50
50
105
105
--
--
--
--
--
--
--
--
--
--
1.6
1.6
1.2
1.2
2.8
2.8
2.8
2.8
322
322
3.5
3.5
187

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3kc83kc4

Table of Contents