7.2.3.5
Outputs of the electronic module
The following outputs are located on the electronic module:
①
②
③
Figure 7-13
Designation
Relay of operational
readiness
Switching the genera-
tor on/off
Display connection
Manual, 08/2017, L1V30368969104A-02
Output – relay of the operational readiness of the device
Output – 3KC9823-0 display (optional)
Output – switching the generator on/off
Outputs of the electronic module
Pin
Explanation
63B
Availability of the electronic module
and of the motor operator:
64B
Open if the electronic module
•
and/or motor operator of the
transfer switching equipment
are not available.
Closed if the switch on the
•
motor operator is at the "Auto"
position and the electronic
module and the motor operator
are ready for operation.
71
Common control terminal for pins
72 and 74
72
Signal for starting / stopping the
generator: NC contact (normally
closed contact)
74
Signal for starting / stopping the
generator: NO contact (normally
open contact)
To display Output for the optional 3KC9823-0
display
7.2 Functions of the inputs and outputs
Properties
Recommended
cable cross-section
Floating contacts 2 A
1.5 - 2.5 mm
AC1 / 250 V
Floating contacts 2 A
1.5 - 2.5 mm
AC1 / 250 V
Cable length up to 3 m RJ45
Operation
2
2