9.1.1

Mounting terminal covers

The following steps are necessary for fitting the terminal covers on the 3KC4 and 3KC8
transfer switching equipment of current ratings 250 A to 630 A.
Note
If bridging bars are used, mount them first.
Requirements
● Main circuit is disconnected
● Transfer switching equipment is in the "Manual" position
● Bridging bars are mounted (if used)
● Accessories for the electronic module installed (3KC8 only)
Procedure
Figure 9-2
1. Connect the terminal covers with each other depending on the number of poles.
2. Place the connected terminal covers in the draw-out assembly of the transfer switching
equipment.
Note
When using bridging bars, only the terminal cover for the front may be used.
Manual, 08/2017, L1V30368969104A-02
Mounting terminal covers
Accessories
9.1 Terminal covers
147