Siemens SENTRON Manual page 212

Transfer switching equipment and load transfer switches
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

Applications
13.4 Transfer between three sources with two outgoing loads
Transfer with T1 (kVA) < T2 (kVA) and T2 (kVA) > T3 (kVA)
As well as the previously described applications, applications comprising 3 transformers (T1,
T2, T3) where the power of the transformer T2 is greater than that of the other two
(T1 (kVA) < T2 (kVA) and T2 (kVA) > T3 (kVA)) can also be implemented with the transfer
switching equipment. By using two transfer switches, this complex application can be
realized, thus enabling the power supply to be maintained.
Figure 13-7
* Dependent on the priority setting on the transfer switching equipment
212
Transfer T1 (kVA) < T2 (kVA) and T2 (kVA) > T3 (kVA)
T1
T2
0
0
1
0
0
1
0
0
1
0
0
1
1
1
1
1
T3
Switching state
of the transfer
switching
equipment
0
x
0
P1
0
P2 + P3
1
P4
1
P1 + P4
1
P2
+ (P3 or P4)*
0
(P1 or P2)*
+ P3
1
(P1 or P2)*
+ (P3 or P4)*
Manual, 08/2017, L1V30368969104A-02
Non-critical
Critical
load 1
load 2
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON