Fault States And Fault Detection On The 3Kc8 Transfer Switching Equipment - Siemens SENTRON Manual

Transfer switching equipment and load transfer switches
Hide thumbs Also See for SENTRON:
Table of Contents

Advertisement

10.1.2

Fault states and fault detection on the 3KC8 transfer switching equipment

Fault state
The transfer switching equipment does not transfer automat-
ically (automatic or remote transfer switching).
The transfer switching equipment cannot be operated with
the handle.
The electrical commands I (ON) – O (OFF) – II (ON) are not
followed.
The transfer switching equipment cannot be locked.
Manual, 08/2017, L1V30368969104A-02
Procedure for fault rectification
Check whether the power supply inputs of terminals 101
and 102 as well as 201 and 202 (208 to
277 V AC ± 20 %) are connected.
Check whether the switch is in the "Auto" position.
Check whether contacts 313 and 317 are opened.
Check whether the "Power" LED shows a green light
and the warning LED has gone out.
Check whether the "Ready" LED on the electronic mod-
ule shows a continuous green light
Check whether at least one of the two LEDs for source
availability shows a continuous green light.
Check product availability via the closed contacts 63A
and 64A as well as 63B and 64B.
Check whether the problem relates to the electronic
module and the motor operator, or only to the electronic
module.
Note: The electronic module can be bypassed to localize the
problem to the electronic module or motor opera-
tor. Contacts 312 and 317 must be closed and contact 313
must remain open.
In this way, the motor operator can execute transfer com-
mands through inputs 314-317 without involvement of the
electronic module. The transfer switching equipment is in
remote mode.
Check whether the switch is in the "Manual" position.
Check whether the product is not padlocked.
Check the direction of movement of the handle.
Try to turn the handle in the direction described on the
handle with appropriate force.
Check the selected control logic (impulse / continuous
operation logic).
Check the cabling of the plug-in connections.
Check whether contacts 312 and 317 are closed.
Check whether contacts 313 and 317 are opened.
Check whether the switch is in the "Manual" position.
Ensure the handle for manual transfer has been re-
moved and is not secured in the assembly.
Check whether the switch on the transfer switching
equipment is in the O position (padlocking mode is only
possible in the O position).
Service and maintenance