KEB COMBIVERT F5 Series Instruction Manual page 25

Control circuit from v3.2
Hide thumbs Also See for COMBIVERT F5 Series:
Table of Contents

Advertisement

Parameter description
CP.35
AN1 Set value selection
Description
The setpoint input 1 (AN1) can be triggered by various signal levels. In order to correctly evaluate the signal, this
parameter must be adapted to the signal source. The settings must be confirm by „ENTER".
Value
Setting
0
x
1
2
CP.36
AN1 zero point hysteresis
Co-domain
-10.0...10.0 %
direction of rotation
0...±10 V DC / Ri = 56 kΩ
0...±20 mA DC / Ri = 250 Ω
4...20 mA DC / Ri = 250 Ω
At the F5-BASIC control at housing type A or B the signal source may not be re-adjusted.
Setting
Description
0,2 %
Through capacitive as well as inductive coupling on the input lines or
voltage fluctuations of the signal source, the motor connected to the
inverter can still drift (tremble) during standstill in spite of the analog
input filter. It is the task of the zero point hysteresis to suppress this.
With parameter CP.36 the analog signal for the input REF can be faded
out in the range of 0...±10 %. The adjusted value is applicable for both
directions of rotation.
If a negative percent value is adjusted the hysteresis acts in addition
to the zero point around the current setpoint. Setpoint changes at
constant running are accepted only if they are larger than the adjusted
hysteresis.
f
CP.11
CP.10
10V
0V
20 mA
0 mA
4 mA
20 mA
U
REF
GB - 25