Parameter description
CP.29
Analog output 1 / Function
CP.29 defines the function of analog output 1. The settings must be confirm by „ENTER".
Value
Setting
0
1
2
x
3
4
5
6
7
8...10
11
12
13
14...18
19
20
21
These values are only present at control type GENERAL !
CP.30 Analog output 1 / amplification
Co-domain
-20,00...20,00
Example:
The analog output shall give out +10 V
at 70 % instead at 100 %.
100 %
CP.30 = –––––– = 1,43
70 %
CP.31
Relay output 1 / function
CP.32
Relay output 2 / function
CP.31 and CP.32 determine the function of the two relay outputs (terminals X2A.24...26 and X2A.27...29). The
values must be confirm by „ENTER".
Value
Setting Function
0
1
2
3
GB - 22
Reaction
Absolute actual frequency (CP.1)
Absolute set frequency (CP.2)
Actual frequency (CP.1)
Set frequency (CP.2)
Output voltage (CP.9)
DC link voltage (CP.7)
Apparent current (CP.4)
Active current
Only application mode
Absoluter active current
Power stage temperature
Motor temperature
Only application mode
Ramp output frequency
Absolute ramp output frequency
Only application mode
Setting
Description
1,00
With the amplification the output voltage of the analog output can be
tuned the signal to be given out. An amplification of 1 corresponds to
±100 % = ±10 V.
No function (generally off)
Generally on
Run signal; also by DC-braking
Ready signal (no error)
out
100%
CP.30
-100%
-100%
Output
100 Hz = 100 %
100 Hz = 100 %
±100 Hz = ±100 %
±100 Hz = ±100 %
500 V = 100 %
1000 V = 100 %
2 x rated current = 100 %
±2 x rated current = ±100 %
2 x rated current = 100 %
100 °C = 100 %
100 °C = 100 %
±100 Hz = ±100 %
100 Hz = 100 %
10V
in
100%
further on next side