Parameter description
Display
rAcc
rdEc
Fcon
rcon
Other status messages are described at the parameters, where they occur (see chapter 4 „Error diagnosis").
CP.04
Apparent current
Co-domain
0...±6553.5 A
CP.05
Apparent current / peak value
Co-domain
0...±6553.5 A
CP.06
Utilization
Co-domain
0.0...200.00 %
CP.07
Intermediate circuit voltage
Display
0...1000 V
CP.08
DC-link voltage / peak value
Display
0...1000 V
CP.09
Output voltage
Co-domain
0...778 V
GB - 14
Status
"Reverse Acceleration" drive accelerates with direction of rotation reverse.
"Reverse Deceleration" drive decelerates with direction of rotation reverse.
"Forward Constant" drive runs with a constant speed and direction of rotation forward.
"Reverse Constant" drive runs with constant speed and direction of rotation reverse.
Description
Display of the actual apparent current in ampere.
Description
CP.5 makes is possible to recognize the max. apparent current. For that the highest value
of CP.4 is stored in CP.5 . The peak value memory can be cleared by pressing the UP,
DOWN or ENTER key or over bus by writing any value you like to the address of CP.5.
The switch off of the inverter also clears the memory.
Description
Display of the actual inverter rate of utilization in percent. 100% rate of utilization is equal
to the inverter rated current. Only positive values are displayed, meaning there is no
differentiation between motor and generatoric operation.
Description
Display of actual DC-link voltage in volt. Typical values:
V-class
Normal operation
230 V
300...330 V DC
400 V
530...620 V DC
Description
CP.8 makes it possible to recognize short-time voltage rises within an operating cycle. For
that the highest value of CP.7 is stored in CP.8. The peak value memory can be cleared
by pressing the UP, DOWN or ENTER key or over bus by writing any value you like to the
address of CP.8. The switch off of the inverter also clears the memory.
Description
Display of the actual output voltage in volt.
Overvoltage (E.OP)
approx. 400 V DC
approx. 800 V DC
Undervoltage (E.UP)
approx. 216 V DC
approx. 240 V DC