Installation Guidelines
2.4

Routing Cables

Routing the Bus Cable
When routing the bus cable indoors, observe the limiting conditions listed in Table 2-1 (d
diameter).
Table 2-1. Limiting Conditions for Routing Cables Indoors
Bending radius when bending once
Bending radius when bending more than once
Permissible temperature range for routing
cables
Temperature range for storing and operating
Do not twist, stretch, or crush cables when routing them.
When routing the bus cable outdoors, observe the general regulations regarding lightning and
grounding.
Lightning protection
If cables for SIMATIC S5 devices are to be laid outdoors, both indoor and outdoor lightning
protection should be provided.
Outside buildings, cables should be laid
in steel conduits grounded at both ends or
in concrete cable ducts with continuous armouring.
Install these elements where the cable enters the building.
Note
Look at each system individually to determine the measures necessary to protect it
against lightning. Please address your questions to your local Siemens representative.
2-8
Feature
Limiting Condition
80 mm (3.1 in.) (10
d
.
160 mm (6.3 in.) (20
.
- 5 °C to+50 °C (+23 °F to+122 °F)
- 30 °C to+65 °C (-22 °F to+149 °F)
S5-95U, SINEC L2
= outer
O
)
O
d
)
O
EWA 4NEB 812 6112-02