S5-95U, SINEC L2
Invoking FB223 and FB224 with the RUP_SINGLE Service in the Receiving PLC
(holds data ready for fetching)
OB1 (Receiving PLC)
.
.
.
.
:JU FB 223
Name :SENDER
ANST :
F
0.0
LSTA :
FY
9
:
:JU FB 224
Name :EMPFANG
EMPF :
F
0.1
:
:
:BE
Invoking FB223 with the SRD Service in the Sending PLC (to fetch the data)
OB1 (Sending PLC)
.
.
.
.
:JU FB 223
Name :SENDER
ANST :
F
0.0
LSTA :
FY
9
:
:
:BE
Storing Request and Confirmation at the Receiver Using the RUP_SINGLE Service
(holding data ready for fetching)
DB33
0:
KH = 0000;
1:
KY = 000,000;
2:
KY = 006,000;
3:
KY = 000,000;
4:
KY = 000,000;
5:
KH = 1111;
6:
KH = 2222;
7:
KH = 3333;
8:
KH = 4444;
9:
KH = 0000;
10:
KY = 001,000;
11:
KY = 006,000;
12:
KY = 000,000;
13:
KY = 000,255;
14:
KH = 0000;
EWA 4NEB 812 6112-02
Data Transmission by Accessing Layer 2 Services
Send request and fetch confirmation ( section 8.4)
Send initiation bit for the RUP_SINGLE service
Flag byte contains the link_status of the confirmation
Fetch INDICATION of the SRD service
Enable receive
Send request and fetch confirmation ( section 8.4)
Send initiation bit for the SRD service
Flag byte contains the link_status of the confirmation
****Request frame, RUP_SINGLE service****
com_class / user_id
service_code / irrelevant
service_class / irrelevant
irrelevant / rem_add_segm
Data bytes 1 and 2
Data bytes 3 and 4
Data bytes 5 and 6
Data bytes 7 and 8
***Confirmation frame, RUP_SINGLE service***
com_class / user_id
service_code / link_status
service_class / irrelevant
irrelevant / rem_add_segm
Explanation
Explanation
Explanation
8-25