Siemens SIMATIC S5 Manual page 157

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-95U, SINEC L2
link_status Message in the Confirmation Header
Value of
Abbreviation
link_status
(PROFIBUS)
00
H
01
H
02
H
03
H
11
H
15
H
*
SAP 64 is defined as the default SAP.
Invoking FB223 for SDA
OB1 (Sending PLC)
.
.
.
.
:JU FB 223
Name :SENDER
ANST :
F
0.0
LSTA :
FY
9
:
:
:BE
EWA 4NEB 812 6112-02
Table 8-5. link_status Message for SDA
ok
Positive acknowledgement, service executed
ue
Negative acknowledgement; remote PLC is in STOP mode
Prerequisite: Destination station is an S5-95U and the connection
has been properly configured at the destination station
rr
Negative acknowledgement; resources of remote FDL control not
available
rs
service_code or rem_add_station not activated at the remote
station
na
No response from remote station or response not plausible
iv
- Illegal parameters in the request header or
- Local station is passive or
- Destination station is own station address or
- If own SAP = default SAP
or
- own SAP default SAP
Send request and fetch confirmation ( section 8.4)
Send initiation bit for the SDN service
Flag byte contains the link_status of the confirmation
Data Transmission by Accessing Layer 2 Services
Meaning
: destination SAP is not default SAP
*
: destination SAP is default SAP
*
Explanation
8-17

Hide quick links:

Advertisement

Table of Contents
loading