Sinec L2 Network With Rs 485 Technology; Distance Table For Rs 485 Technology - Siemens SIMATIC S5 Manual

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

System Description
PLC
PLC
PLC
PLC
e.g., S5-95U programmable controller
SINEC L2 bus connector
SINEC L2 bus connector with switched-on terminating resistor
RS 485 repeater with switched-on terminating resistor
Figure 1-15. SINEC L2 Network with RS 485 Technology
The conditions for installing the network are as follows:
You can connect a maximum of 127 stations (TLN 0 is reserved for a programmer).
A maximum of 32 bus loads is permitted per segment (a bus load is either a station or a
repeater).
You can connect a maximum of 7 repeaters in series.
Table 1-7 shows the possible distances between stations calculated on the basis of the expansion
of a bus segment and of the condition specified above that a maximum of 7 repeaters is allowed
between two stations.
Baud Rate in
Kbits/s
1
9.6; 19.2; 93.75
1.2 km
187.5
1.0 km
500
0.4 km
1500
0.2 km
Caution
!
In extensive networks, the potential difference between two stations may be more than
± 7 V. In such a case, take the necessary equipotential bonding measures, otherwise
the SINEC L2 interface will be destroyed.
1-22
PLC
PLC
Table 1-10. Distance Table for RS 485 Technology
Number of Segments Connected in Series
2
3
2.4 km
3.6 km
2.0 km
3.0 km
0.8 km
1.2 km
0.4 km
0.6 km
4
5
6
4.8 km
6.0 km
7.2 km
4.0 km
5.0 km
6.0 km
1.6 km
2.0 km
2.4 km
0.8 km
1.0 km
-
S5-95U, SINEC L2
PLC
PLC
PLC
PLC
7
8
8.4 km
9.6 km
7.0 km
8.0 km
2.8 km
3.2 km
-
-
EWA 4NEB 812 6112-02