Defining The Arguments Of The Basic Parameters For The S5-95U In Conjunction With The Cp 5410 And/Or Cp 5430-1; Basic Parameter Arguments For The S5-95U In Conjunction With Other Simatic Devices - Siemens SIMATIC S5 Manual

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

System Description
Communications with the CP 5410 and/or CP 5430-1
You must set the same basic parameters BDR, SET, ST, SDT 1 and SDT 2 for the S5-95U, CP
5410 and CP 5430-1.
Define the arguments of the BDR, SET, ST, SDT 1 and SDT 2 basic parameters as shown in Table
1-4:
for the S5-95U in DB1
for the CP 5410
for the CP 5430-1
Table 1-4. Defining the Arguments of the Basic Parameters for the S5-95U in Conjunction
Baud rate
Basic
in kbaud
parameters
in bit time units
SET
ST
SDT 1
SDT 2
Example:
Define the baud rate as 187.5 kbaud in DB1. This gives the other basic parameters
as follows: SET 1
Communications with Other SIMATIC Devices, e.g. the CP 5412 or CP 5430-0
You must set the same basic parameters BDR, SET, ST, SDT 1 and SDT 2 for the S5-95U and the
other SIMATIC device.
Define the arguments of the BDR, SET, ST, SDT 1 and SDT 2 basic parameters as shown in Table
1-5:
for the S5-95U in DB1
for the other SIMATIC device
Table 1-5. Basic Parameter Arguments for the S5-95U in Conjunction with
Baud rate
Basic
in kbaud
parameters
in bit time units
SET
ST
SDT 1
SDT 2
Example:
Define the baud rate as 187.5 kbaud in DB1. This gives the other basic parameters
as follows: SET 80
1-12
with the CP 5410 and/or CP 5430-1
9.6
19.2
1
1
80
80
12
12
40
60
ST 380
SDT 1 12
Other SIMATIC Devices
9.6
19.2
10
15
100
170
12
15
60
65
ST 400
SDT 1 80
93.75
187.5
1
1
190
380
12
12
80
150
SDT 2 150.
93.75
187.5
45
80
45
240
400
45
80
200
360
SDT 2 360.
S5-95U, SINEC L2
500
1500
1
60
1000
3600
12
150
360
980
500
1500
80
80
1000
3000
80
150
360
980
EWA 4NEB 812 6112-02