Setting The L2 Basic Parameters On The Programmer; Activating An Editing Path - Siemens SIMATIC S5 Manual

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Programmer Functions Over the SINEC L2 Network
9.5

Setting the L2 Basic Parameters on the Programmer

The following display appears when you press <F1> (SET SYSID) in the "FUNCTION
SELECTION/DEFAULTS" screen:
S Y S I D
LAN PARAMETERS :
L2 NODE ADDRESS :
BAUD RATE :
SLOT
TIME (WAIT FOR RECEIVE):
QUIET TIME (MODEM):
SETUP TIME:
SHORTEST STATION DELAY (SH. PROTOCOL PROC. TIME):
LONGEST STATION DELAY (LO. PROTOCOL PROC.TIME):
TARGET
ROTATION
GAP
UPDATE FACTOR (1 - 100):
HIGHEST L2 STATION ADDRESS:
DEFAULT SAP:
PHYSICAL BUS CHARACTERISTICS:
F1
SET SYSID
The parameters shown are CP-L2 default parameters in the programmer, and must be matched to
the basic L2 parameters of the system ( Table 1-4, 1-5)!
Position the cursor to the parameter you want to change. You can select the baud rate and the
physical bus characteristics with <F3>.
Press <F1> (SET SYSID) to confirm and save the parameters you have changed.
9.6
Activating an Edited Path
You must always match the basic L2 parameters of the CP-L2 to the basic L2 parameters of the
system before activating a path starting at a programmer with an integral CP-L2 communications
processor ( section 9.5).
You can activate an edited path
in the BUS DIALLING utility ( FUNCTION SELECTION screen)
or
in an S5 program package with a path selection facility.
Activating a path establishes a communications link to a remote station.
9-10
C P
L 2
(L O C A L)
(PLEASE REMEMBER THAT EACH INCORRECT MODIFICATION OF
THE DEFAULT VALUES CAN IMPAIR THE OPERABILITY OF THE
NETWORK)
TIME:
F2
F3
SELECT
Figure 9-8. "SYSID CP L2 (LOCAL)" Screen
F4
F5
F6
S5-95U, SINEC L2
0
187.5 KBD
400
50
80
80
400
5000
20
31
57
RS 485
F7
F8
EWA 4NEB 812 6112-02