Siemens SIMATIC S5 Manual page 195

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

DB1 Parameters, DB1 PAFE, TRT
Error Code of DB1
Interpreter (left
byte in data
word or flag word)
21
L2 basic parameter: TLN (station address) of an active station can be only
H
1 to 31
22
L2 basic parameter: TLN (station address) is higher than HSA (highest station
H
address)
23
The connection has been configured to own station
H
24
PLC to PLC connection to a passive station is not possible; or, with standard
H
connection, there is no send mailbox for a passive station.
25
FMA service MAC_EVENT has been activated (DB1 parameter FMAE y), but
H
"STB 200" was not entered
26
L2 basic parameter: SET must be longer than SDT1
H
27
No receive mailbox was specified for the standard connection
H
28
No send mailbox was specified for the standard connection
H
29
L2 basic parameter missing; all basic parameter must be present in DB1
H
parameter block "SL2:".
30
There are several "SL2:" parameter blocks
H
31
L2 basic parameter: SDT2 must be (35+2 times SET)
H
32
L2 basic parameter: (ST - 15) must be SDT2
H
40
ZP master: no data block was specified in DB1 for ZP (ZP DB)
H
41
ZP master: ZP master was entered for a passive station
H
42
ZP master: ZP master has no ZP connection
H
43
ZP master: at least in one ZP connection the ZP slave address is wrong (ZP
H
slave address=ZP master address)
44
ZP master: the ZP connection was assigned twice
H
45
ZP master: The ZPA (ZP output area) was not entered consistently (without
H
gaps) in ZPDB
46
ZP master: length error in ZPA (ZP output area)
H
47
ZP master: The ZPE (ZP input area) was not entered consistently (without
H
gaps) in ZPDB or overlaps.
48
ZP master: length error in ZPE (ZP input area)
H
49
ZP master: ZPA and ZPE overlap in ZP DB
H
52
ZP slave: no data block was specified in DB1 for ZP (ZP DB)
H
53
ZP slave: neither ZPA nor ZPE were specified in DB1
H
54
ZP slave: ZPA and ZPE overlap in ZP DB
H
A-8
Significance
(
SET >
S5-95U, SINEC L2
SDT 1 - 35
)
2
EWA 4NEB 812 6112-02

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinec l2S5-95u

Table of Contents