Prerequisites

Operating steps

Building Technologies Division
Infrastructure & Cities Sector

27.4 Initial PWM parameter settings

27.4.1 Initial settings of PWM basic parameters

Note:
The initial settings of the PWM basic parameter are made exclusively on the OEM
level.
Operating unit AZL2... for setting the parameters is connected
Unit is wired up in accordance with the proposed application
Mains voltage is available
Safety loop is closed
There is no heat request, unit is in standby (OFF)
Fan parameters, such as maximum speed and Hall signal (number of pulses per
revolution) are known
With unprogrammed program module (initial settings), AZL2... displays OFF UPr
With unprogrammed program module (initial settings), the onboard operating panel
of the LME7... displays UPr
Select programming mode for OEM
Press
and
A
F
Enter the OEM's password via
password
Display shows PArA and then 400: SEt. Confirm by pressing
Unit jumps to setting parameter P0 (ignition load position) 516.00 (516 blinking).
Keep
depressed for >1 second. Subindex 00 is blinking
/reset
Keep
depressed for >1 second. Display changes to -. Also see chapter
/reset
Setting parameters with index, with or without direct display
By pressing
or
required minimum limit speed for the ignition load position at which the burner can
still be safely ignited
Press
to transfer the setting value to the onboard memory
/reset
ESC
By pressing
and return to the selection level for the subindex
Subindex 00 blinks. Press
Press
for >1 second. Display changes to -
/reset
By pressing
or
required maximum limit speed for the ignition load position at which the burner may
still be safely ignited
Press
to transfer the setting value to the onboard memory
/reset
ESC
By pressing
entry level and return to the selection level for the parameter number
Basic Documentation LME7...
27 PWM settings
simultaneously for <5 seconds. Display shows CodE
,
and
the speed can be changed in step sizes of 10 rpm. Set the
(press
and
simultaneously) you leave the entry level
to select the next subindex. Subindex 01 blinks
the speed can be changed in step sizes of 10 rpm. Set the
twice (press
and
. Also see chapter Entering the
/reset
/reset
simultaneously) you leave the
225/245
CC1P7105en
29.11.2011