Table 6: Holding Registers For Modbus Queries - Gamatronic Centric 3x480 Vac User Manual

Ups system
Hide thumbs Also See for Centric 3x480 Vac:
Table of Contents

Advertisement

(Note: these registers can be addressed as either holding registers [for example, 4x0002] or input registers [for example, 3x0002])
Register
Variable name
1 4x0001 Battery Condition
2 4x0002 Battery Status
3 4x0003 Battery Charge
4 4x0004 Seconds On Battery
5 4x0005 Estimated Minutes
6 4x0006 Estimated Charge
7 4x0007 Battery Voltage
8 4x0008 Battery Current
9 4x0009 Battery Temperature
11 4x0011 Input Lines Number
12 4x0012 Input Frequency Line 1
13 4x0013 Input Voltage Line 1
14 4x0014 Input Current Line 1
16 4x0016 Input Frequency Line 2
17 4x0017 Input Voltage Line 2
18 4x0018 Input Current Line 2
20 4x0020 Input Frequency Line 3
21 4x0021 Input Voltage Line 3
G
E
AMATRONIC
LECTRONIC

Table 6: Holding Registers for Modbus queries

GET Values
0: Good
1: Weak
2: Replace
0: Battery OK
Has effect only during power failure (battery discharge), "Battery low" usually comes
1: Battery Low
minutes before the UPS batteries are depleted and it switches off
2: Battery Depleted
0: Floating
Most common situation is "floating" as a constant state, however this depends on the
1: Charging
UPS topology
2: Resting
3: Discharging
seconds
Has effect only during power failure
minutes
Mathematical estimation of available backup time
0-100%
Mathematical estimation of battery charge in percents
×10 Vdc
Divide the value by 10 for real measurement: 485/10=48.5 Vdc
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
°C
Degrees centigrade
1 to 3
Number of the UPS input phases
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
CENTRIC 3x480, User Guide, rel. 1.7
I
L
.
NDUSTRIES
TD
Remarks
51

Advertisement

Table of Contents
loading

This manual is also suitable for:

Centric 240 kwCentric 120 kw

Table of Contents