1MRS755972
5.1.4.7.
Table 5.1.4.7.-1
Setting values
Setting
Description
59P-1
Pickup value of element 59P-1
59P-1 TDLY
Operate time of element 59P-1
59P-1 MODE
Operation mode setting for 59P-1
59P-1 TD
IDMT time dial 59P-1 TD
59P-1 RSET
Resetting time of element 59P-1
59P-1 D/P
Drop-off/pick-up ratio of element 59P-1
U
/U
MODE
U
/U
mode setting of elements 59P-2 and
1
2
1
2
27P-2
59P-2
Pickup value of element 59P-2
47
Pickup value of element 47
59P-2 TDLY
Operate time of element 59P-2
59P-2/U
MODE Operation mode setting for 59P-2/U
2
59P-2 TD
IDMT time dial 59P-2 TD
27P-1
Pickup value of element 27P-1
27P-1 TDLY
Operate time of element 27P-1
Voltage Relay
Technical Reference Manual - ANSI Version

Settings

There are two alternative setting groups available, setting groups 1 and 2.
Either of these setting groups can be used as the actual settings, one at a time.
Both groups have their related registers. By switching between the setting
groups, a whole group of settings can be changed at the same time. This can
be done in any of the following ways:
Via the HMI
*
Entering SPA parameter V150 via serial communication
*
Via a digital input
*
Switching between setting groups via a digital input has a higher
priority than via the HMI or with the parameter V150.
The setting values can be altered via the HMI or with a PC provided with
Relay Setting Tool.
Before the relay is connected to a system it must be assured that the relay has
been given the correct settings. If there is any doubt, the setting values should
be read with the relay trip circuits disconnected or tested with current
injection; refer to Chapter 7.-4-Disturbance recorder parameters for
additional information.
2
Setting range
0.6...1.4 × U
(VT)
n
0.06...600 s
0 = definite time
1 = curve A
2 = curve B
0.05...2.00
0.07...60.0 s
0.95...0.99
0 = 59P-2 and 27P-2
1 = 59P-2 and 27D
2 = 47 and 27P-2
0.80...1.60 × U
(VT)
n
0.05...1.00 × U
(VT)
n
0.05...600 s
0 = definite time
1 = curve A
2 = curve B
0.05...2.00
0.20...1.20 × U
(VT)
n
0.10...600 s
REU 610
Default setting
1.2
0.06
0
0.05
0.07
0.97
0
1.2
0.05
0.05
0
0.05
0.2
0.1
35