ABB REU 610 Technical Reference Manual page 44

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
Table 5.1.4.7.-8
SGR1...SGR8 (Continued)
Switch
Function
SGR1...8/11 Pickup signal from element 59N-2
SGR1...8/12 Trip signal from element 59N-2
SGR1...8/13 External trip signal
ΣSGR1...8
If the optional I/O module has not been installed, dashes are shown on the LCD and "9999" when the parameter is read via the SPA
a)
bus.
44
Voltage Relay
Technical Reference Manual - ANSI Version
SGL1...SGL8
The signals are routed to LED1 with the switches of switchgroup SGL1, to
LED2 with those of SGL2, and so forth.
Table 5.1.4.7.-9
SGL1...SGL8
Switch
Function
SGL1...8/1
Trip signal from element 59P-1
SGL1...8/2
Trip signal from element 59P-2 or 47
SGL1...8/3
Trip signal from element 27P-1
SGL1...8/4
Trip signal from element 27P-2 or 27D
SGL1...8/5
Trip signal from element 59N-1
SGL1...8/6
Trip signal from element 59N-2
SGL1...8/7
Trip lockout signal
SGL1...8/8
DI1 signal
SGL1...8/9
DI2 signal
SGL1...8/10
DI3 signal
SGL1...8/11
DI4 signal
SGL1...8/12
DI5 signal
ΣSGL1...SGL8
New trip target timer
The new trip target timer can be configured to allow a second trip target on
the LCD. When several protection elements trip, the first trip target is
displayed until the time, as specified by the NEW TRIP IND. setting value,
has expired. After this, a new trip target can displace the old one. The basic
protection functions are not affected by the NEW TRIP IND. setting.
Default setting
SGR1...SGR3
SGR4...SGR5
0
1
0
2730
1365
1MRS755972
SGR6...SGR8
1
0
0
0
0
0
0
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0