1MRS755972
Table footnotes from previous page
a)
When the switch is on, the phase(s) that caused the pickup are shown on LCD.
Table 5.1.4.7.-4
SGF3
Switch
Function
SGF3/1
Disabling of element 59P-2 or 47
SGF3/2
Disabling of element 27P-2 or 27D
SGF3/3
Disabling of element 59N-1
SGF3/4
Disable of element 59N-2
When the switch is in position 1, the element is disabled.
*
ΣSGF3
Table 5.1.4.7.-5
SGF4
Switch
Function
SGF4/1
Selecting single-phase or three-phase use
0 = three-phase use
*
1 = single-phase use
*
SGF4/2
Internal blocking of pickup and trip of element 27P-1 when one of the measured phase-to-
phase voltages fall below 0.15 ×U
0 = internal blocking of pickup and trip of element 27P-1
*
1 = no internal blocking of pickup and trip of element 27P-1
*
SGF4/3
Internal blocking of pickup and trip of element 27P-2 or 27D when one of the measured phase-
to-phase voltages falls below 0.15 × U
0 = internal blocking of pickup and trip of element 27P-2 or 27D
*
1 = no internal blocking of pickup and trip of element 27P-2 or 27D
*
SGF4/4
Blocking of element 27P-1 tripping by the pickup of element 27P-2 or 27D
0 = tripping of element 27P-1 is not blocked
*
1 = tripping of element 27P-1 is blocked
*
SGF4/5
Start and trip criteria for element 59P-1
0 = element operates when one of the phase-to-phase voltages rise above the set pickup
*
value.
1 = element operates when all the phase-to-phase voltages rise above the set pickup value
*
SGF4/6
Start and trip criteria for element 59P-2
0 = element operates when one of the phase-to-phase voltages rise above the set pickup
*
value.
1 = element operates when all the phase-to-phase voltages rise above the set pickup value.
*
Voltage Relay
Technical Reference Manual - ANSI Version
a)
When single-phase use is selected, the measured voltage has to be connected
to inputs X2.1-1 and X2.1-2. Additionally, the U
overridden and the negative phase-sequence protection mode and positive
phase-sequence protection mode are not in use.
(VT).
n
(VT)
n
a)
a)
This switch has no effect if the element 59P-2 is based on negative phase-
sequence calculation.
REU 610
/U
mode setting S7 is
1
2
Default setting
0
0
0
0
0
Default setting
0
0
0
0
0
0
39