1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
Table 5.1.17.1.-1 Event masks
Event mask
Code
V155
E31...E34
1V155
1E1...1E16
1V156
1E17...1E24
1V157
1E25...1E30
2V155
2E1...2E16
2V156
2E17...2E26
Channel 0
Events always included in the event reporting:
Table 5.1.17.1.-2 Event codes E1...E4
Channel
Event
Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
Table 5.1.17.1.-3 Event codes E50...E51
Channel
Event
Description
0
E50
Relay restart
0
E51
Event buffer overflow
Events possible to mask out:
Table 5.1.17.1.-4 Event codes E31...E34
Channel
Event
Description
0
E31
Disturbance recorder triggered
0
E32
Disturbance recorder memory cleared
0
E33
HMI password opened
0
E34
HMI password closed
Default value of event mask V155
Setting range
Default setting
0...15
1
0...65535
21845
0...255
85
0...63
1
0...65535
3
0...1023
0
Weight-
ing
factor
1
2
4
8
REU 610
Default
value
1
0
0
0
1
105