1MRS755972
Table 5.1.4.7.-7
SGB1...SGB5
Switch
Function
SGB1...5/1
0 = targets are not cleared by the digital input signal
*
1 = targets are cleared by the digital input signal
*
SGB1...5/2
0 = targets are not cleared and latched output contacts are not unlatched by the digital input
*
signal
1 = targets are cleared and latched output contacts are unlatched by the digital input signal
*
SGB1...5/3
0 = targets and memorized values are not cleared and latched output contacts are not
*
unlatched by the digital input signal
1 = targets and memorized values are cleared and latched output contacts are unlatched by
*
the digital input signal
SGB1...5/4
Switching between setting groups 1 and 2 by using the digital input
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input. When the digital input is
*
energized, setting group 2 is activated, if not, setting group 1 is activated.
SGB1...5/5
Time synchronization by the digital input signal
SGB1...5/6
External tripping by the digital input signal
SGB1...5/7
External triggering of the CBFAIL by the digital input signal
SGB1...5/8
External triggering of the trip lockout by the digital input signal
SGB1...5/9
Resetting of the trip lockout by the digital input signal
SGB1...5/10
Blocking of tripping of element 59P-1 by the digital input signal
SGB1...5/11
Blocking of tripping of element 59P-2 or 47 by the digital input signal
SGB1...5/12
Blocking of tripping of element 27P-1 by the digital input signal
SGB1...5/13
Blocking of tripping of element 27P-2 or 27D by the digital input signal
SGB1...5/14
Blocking of tripping of element 59N-1 by the digital input signal
SGB1...5/15
Blocking of tripping of element 59N-2 by the digital input signal
ΣSGB1...5
Voltage Relay
Technical Reference Manual - ANSI Version
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of
switchgroup SGB1, the DI2 signal with those of SGB2, and so forth.
When SGB1...5/4 is set to 1, it is important that the switch has the same setting
in both setting groups.
SGR1...SGR8
The pickup, trip and alarm signals from the protection elements and the
external trip signal are routed to the output contacts with the switches of
switchgroups SGR1...SGR8.
The signals are routed to PO1...PO3 with the switches of switchgroup
SGR1...SGR3 and to SO1...SO5 with those of SGR4...SGR8.
REU 610
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
41