ABB REU 610 Technical Reference Manual page 36

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
Table 5.1.4.7.-1
Setting values (Continued)
Setting
Description
27P-1 MODE
Operation mode setting for 27P-1
27P-1 TD
IDMT time dial 27P-1 TD
27P-1 RSET
Resetting time of element 27P-1
27P-1 D/P
Drop-off/pick-up ratio of element 27P-1
27P-2
Pickup value of element 27P-2
27D
Pickup value of element 27D
27P-2 TDLY
Operate time of element 27P-2
27P-2/U
MODE Operation mode setting for 27P-2/U
1
27P-2 TD
IDMT time dial 27P-2 TD
59N-1
Pickup value of element 59N-1
59N-1 TDLY
Operate time of element 59N-1
59N-1 RSET
Resetting time of element 59N-1
59N-2
Pickup value of element 59N-2
59N-2 TDLY
Operate time of element 59N-2
Trip fail
Operate time of CBFAIL
36
Voltage Relay
Technical Reference Manual - ANSI Version
1
Switchgroups and parameter masks
The settings can be altered and the functions of the relay selected in the SG_
selector switchgroups. The switchgroups are software based and thus not
physical switches to be found in the hardware of the relay. A checksum is
used for verifying that the switches have been properly set. The
Fig. 5.1.4.7.-1 shows an example of manual checksum calculation.
Setting range
0 = definite time
1 = curve C
0.10...2.00
0.07...60.0 s
1.01...1.05
0.20...1.20 × U
(VT)
n
0.20...1.20 × U
(VT)
n
0.10...600 s
0 = definite time
1 = curve C
0.10...2.00
2.0...80.0% U
(VT)
n
0.10...600 s
0.07...60.0 s
2.0...80.0% U
(VT)
n
0.10...600 s
0.10...60.0 s
1MRS755972
Default setting
0
0.1
0.07
1.03
0.2
0.3
0.1
0
0.1
2.0
0.1
0.07
2.0
0.1
0.10

Advertisement

Table of Contents