ABB REU 610 Technical Reference Manual page 97

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755972
Table 5.1.17.-7 Control parameters (Continued)
Description
Testing the self-supervision
LED test for pickup and trip targets
LED test for programmable LEDs
Trip-circuit supervision
Nominal voltage
Remote control of setting group
Event mask for E31...E34
Event mask for 1E1...1E16
Event mask for 1E17...1E24
Event mask for 1E25...1E30
Event mask for 2E1...2E16
Event mask for 2E17...2E26
Entering the SPA password for settings
Changing the SPA password or taking the
password protection into use
Changing the HMI password
Clearing trip counters 59P-1 and 59P-2; 27P-
1 and 27P-2, 59N-1 and 59N-2, External trips
Restoring factory settings
Warning code
IRF code
Unit address of the relay
Data transfer rate (SPA), kbps
Rear communication
Rear communication protocol
Connection type
Line-idle state
Voltage Relay
Technical Reference Manual - ANSI Version
Parameter
V109
V110
V111
V113
V134
V150
V155
1V155
1V156
1V157
2V155
2V156
V160
V161
V162
V166
V167
V168
V169
V200
V201
V202
b)
V203
V204
V205
R, W, P
Value
W (P)
1 = Self-supervision output contact is
activated and the READY target LED
starts to blink
0 = Normal operation
R, W (P)
0 = Pickup and trip LEDs off
1 = Trip LED on, pickup LED off
2 = Pickup LED on, trip LED off
3 = and trip LEDs on
R, W
0...255
R, W
0 = Not in use
1 = In use
R, W (P)
0 = 100 V
1 = 110 V
2 = 115 V
3 = 120 V
R, W
0 = Setting group 1
1 = Setting group 2
R, W
0...15
R, W
0...65535
R, W
0...255
R, W
0...63
R, W
0...65535
R, W
0...1023
W
1...999
W (P)
1...999
W
1...999
W (P)
1 = Clear trip counters
W (P)
2 = Restore factory settings for CPU
3 = Restore factory settings for DNP
a)
R
0...65535
a)
R
0...255
R, W
1...254
R, W
9.6/4.8
W
1 = Rear connector activated
R, W
0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
4 = DNP 3.0 (read-only)
R, W
0 = Loop
1 = Star
R, W
0 = Light off
1 = Light on
REU 610
97