ABB REU 610 Technical Reference Manual page 127

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
Table 5.2.3.-12 Standard tests
Insulation tests:
Dielectric tests
-Test voltage
Impulse voltage test
-Test voltage
Insulation resistance measurements
-Isolation resistance
Mechanical tests:
Vibration tests (sinusoidal)
Shock and bump test
Table 5.2.3.-13 Data communication
Rear interface, connector X5.3, X5.4, X5.5 or X5.8:
-Fiber-optic or RS-485 connection
-SPA bus, IEC 60870-5-103, DNP 3.0 or Modbus protocol
-9.6 or 4.8 kbps (additionally 2.4, 1.2 or 0.3 kbps for Modbus)
Front interface:
-Optical connection (infrared): wirelessly or via the front communication cable
(1MRS050698)
-SPA bus protocol
-9.6 or 4.8 kbps (9.6 kbps with front communication cable)
Auxiliary voltage
The relay requires a secured auxiliary voltage supply to operate. The internal
power supply of the relay forms the voltages required by the relay electronics.
The power supply is a galvanically isolated (flyback-type) DC/DC converter.
When the auxiliary voltage is connected, the green target LED (ready) on the
front panel is lit. For detailed information on power supply, refer to
Table 5.2.3.-2.
The primary side of the power supply is protected with a fuse located on the
printed circuit board of the relay.
According to IEC 60255-5
2 kV, 50 Hz, 1 min
According to IEC 60255-5
5 kV, unipolar impulses, waveform
1.2/50 μs, source energy 0.5 J
According to IEC 60255-5
>100 MΩ, 500 V DC
According to IEC 60255-21-1, class I
According to IEC 60255-21-2, class I
REU 610
127