Table 5.1.4.7.-2
SGF1 (Continued)
Switch
Function
SGF1/3
Selection of the latching feature for PO3
When the switch is in position 0 and the measuring signal which caused the trip falls below
*
the set pickup value, the output contact returns to its initial state.
When the switch is in position 1, the output contact remains active although the measuring
*
signal which caused the trip falls below the set pickup value.
A latched output contact can be unlatched either via the HMI, a digital input or the serial bus.
SGF1/4
Minimum pulse length for SO1 and SO2 and optional SO3, SO4 and SO5
0 = 80 ms
*
1 = 40 ms
*
SGF1/5
Minimum pulse length for PO1, PO2 and PO3
0 = 80 ms
*
1 = 40 ms
*
SGF1/6
CBFAIL
0 = CBFAIL is not in use
*
1 = the signal to PO1 pickups a timer which generates a delayed signal to PO2, provided that
*
the fault is not cleared before the CBFAIL operate time has elapsed
SGF1/7
Trip lockout function
0 = the trip lockout function is not in use. PO3 works as a normal power ouput relay.
*
1 = the trip lockout function is in use. PO3 is dedicated to this function.
*
SGF1/8
External fault warning
When the switch is in position 1, the warning signal from the trip-circuit supervision is routed
*
to SO2.
ΣSGF1
Table 5.1.4.7.-3
SGF2
Switch
Function
SGF2/1
Operation mode of the pickup target of element 59P-1
SGF2/2
Operation mode of the trip target of element 59P-1
SGF2/3
Operation mode of the pickup target of element 59P-2 or 47
SGF2/4
Operation mode of the trip target of element 59P-2 or 47
SGF2/5
Operation mode of the pickup target of element 27P-1
SGF2/6
Operation mode of the trip target of element 27P-1
SGF2/7
Operation mode of the pickup target of element 27P-2 or 27D
SGF2/8
Operation mode of the trip target of element 27P-2 or 27D
SGF2/9
Operation mode of the pickup target of element 59N-1
SGF2/10
Operation mode of the trip target of element 59N-1
SGF2/11
Operation mode of the pickup target of element 59N-2
SGF2/12
Operation mode of the trip target of element 59N-2
0 = the trip target is automatically cleared after the fault has disappeared.
*
1 = latching. The trip target remains active although the fault has disappeared.
*
ΣSGF2
38
Voltage Relay
Technical Reference Manual - ANSI Version
The latching feature being selected for PO1, PO2 and PO3 overrides this
function.
a)
a)
a)
a)
a)
a)
1MRS755972
Default setting
0
0
0
0
0
0
0
Default setting
0
1
0
1
0
1
0
1
0
1
0
1