ABB REU 610 Technical Reference Manual page 95

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755972
Table 5.1.17.-4 Parameters for the disturbance recorder (Continued)
Description
External trigger signal's edge
Checksum of external signal storing mask V243
Triggering state, clearing and restart
M1 can be used for broadcast triggering by using the unit address "900".
a)
b)
Parameters can be written if the recorder has not been triggered.
c)
The disturbance recorder requires this parameter to be set. The conversion factor is the transformation ratio multiplied by the rated of
the relay.If this parameter is set to zero, the disturbance recorder data cannot be analyzed and dashes are shown on the LCD instead
of the primary values.
d)
This value is copied to parameters M81 and M82.
Voltage Relay
Technical Reference Manual - ANSI Version
Parameter (channel 0)
V242
b)
V246
Table 5.1.17.-5 Disturbance recorder internal triggering and storing
Event
Weighting
59P-1
Trip of element 59P-
1
59P-2 or 47
Trip of element 59P-
2 or 47
27P-1
Trip of element 27P-
1
27P-2 or 27D
Trip of element 27P-
2 or 27D
59N-1
Trip of element 59N-
1
59N-2
Trip of element 59N-
2
Σ
R, W
R, W
R, W
R, W
Default value
factor
of triggering
mask, V236
1
0
2
1
4
0
8
1
16
0
32
1
64
0
128
1
256
0
512
1
1024
0
2048
1
682
REU 610
Value
0...31
0...31
R:
0 = Recorder not
triggered
1 = Recorder triggered
and recording stored in
the memory
W:
0 = Clear recorder
memory
2 = Download restart;
sets the first information
and the time stamp for
triggering ready to be
read
4 = Manual triggering
Default value
Default value
of triggering
of storing
a)
edge, V237
mask, V238
0
0
0
1
0
1
0
1
0
0
0
1
0
1
0
1
0
0
0
1
0
0
0
0
0
751