ABB REU 610 Technical Reference Manual page 70

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
Table 5.1.15.2.-7 Mapping of Modbus data: analog data
Description
Phase-to-phase voltage U
Phase-to-phase voltage U
Phase-to-phase voltage U
Residual voltage U
n
Positive phase-sequence voltage
Negative phase-sequence voltage
Table 5.1.15.2.-8 Mapping of Modbus data: digital data
Description
Pickup signal from element 59P-1
Pickup signal from element 59P-1 CD
Trip signal from element 59P-1
Trip signal from element 59P-1 CD
Pickup signal from element 59P-2
Pickup signal from element 59P-2 CD
Trip signal from element 59P-2
Trip signal from element 59P-2 CD
Pickup signal from element 27P-1
Pickup signal from element 27P-1 CD
Trip signal from element 27P-1
Trip signal from element 27P-1 CD
Pickup signal from element 27P-2
Pickup signal from element 27P-2 CD
Trip signal from element 27P-2
Trip signal from element 27P-2 CD
Pickup signal from element 59N-1
Pickup signal from element 59N-1 CD
Trip signal from element 59N-1
Trip signal from element 29N-1 CD
Pickup signal from element 59N-2
Pickup signal from element 59N-2 CD
Trip signal from element 59N-2
Trip signal from element 59N-2 CD
Trip lockout
Trip lockout CD
External trip
External trip CD
CBFAIL
70
Voltage Relay
Technical Reference Manual - ANSI Version
HR/IR
address (.bit)
404
ab
405
bc
406
ca
407
408
409
HR/IR
address (.bit)
410.00
410.01
410.02
410.03
410.04
410.05
410.06
410.07
410.08
410.09
410.10
410.11
410.12
410.13
410.14
410.15
411.00
411.01
411.02
411.03
411.04
411.05
411.06
411.07
411.08
411.09
411.10
411.11
411.12
DI/Coil bit
Writeable
address
DI/Coil bit
Writeable
address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
1MRS755972
Value
Comment
range
0...200
0...2 × U
(VT)
n
0...200
0...2 × U
(VT)
n
0...200
0...2 × U
(VT)
n
0...200
0...200% U
(VT)
n
0...200
0...2 × U
(VT)
n
0...200
0...2 × U
(VT)
n
Value
Comment
range
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated

Advertisement

Table of Contents
loading

Table of Contents