ABB REU 610 Technical Reference Manual page 56

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
56
Voltage Relay
Technical Reference Manual - ANSI Version
Table 5.1.12.-1 Recorded data
REGISTER Data description
EVENT1
Phase-to-phase voltage U
*
the rated voltage, U
voltages U
Residual voltage U
*
rated voltage U
Maximum voltage value of the phase-to-phase voltages during the last
*
fault conditions in the network, measured as a multiple of the rated
voltage U
n
Minimum voltage value of the phase-to-phase voltages during the last
*
fault conditions in the network, measured as a multiple of the rated
voltage U
n
Maximum voltage value of the negative phase-sequence voltage
*
during the last fault conditions in the network, measured as a multiple
of the rated voltage U
phase-sequence voltage U
when read via serial communication.
Minimum voltage value of the positive phase-sequence voltage during
*
the last fault conditions in the network, measured as a multiple of the
rated voltage U
phase-sequence voltage U
when read via serial communication.
Maximum voltage value of the residual voltage U
*
conditions in the network, measured as a percentage of the rated
voltage U
n
Duration of the last pickup of elements 59P-1, 59P-2/47, 27P-1, 27P-
*
2/27D, 59N-1, 59N-2 and of the external trip, shown as a percentage
of the set operate time, or of the calculated operate time at IDMT
characteristic. A value other than zero indicates that the
corresponding element has picked up whereas a value which is 100%
of the set or calculated operate time indicates that the operate time of
the element has elapsed, that is, the element has tripped. If the
operate time of a element has elapsed but the element is blocked, the
value is 99% of the set or calculated operate time.
Time stamp for the event. The time when the collected data was
*
stored. The time stamp is displayed in two registers, one including the
date expressed as yy-mm-dd, and the other including the time
expressed as HH.MM;SS.sss.
EVENT 2
Same as EVENT 1.
EVENT 3
Same as EVENT 1.
EVENT 4
Same as EVENT 1.
EVENT 5
Same as EVENT 1.
Number of
The number of times each protection element 59P-1, 59P-2/47, 27P-1,
pickups
27P-2/27D, 59N-1, 59N-2 has picked up, counting up to 999.
Number of
Number of trips:
trips
*
Overvoltage elements 59P-1, 59P-2 and 47
Undervoltage elements 27P-1, 27P-2 and 27D
*
Residual overvoltage elements 59N-1 and 29N-2
*
External trip
*
When the counters reach their maximum values (65535), they roll over.
measured at a time of trip as a multiple of
ab
(VT). The same applies to phase-to-phase
n
and U
.
bc
ca
measured at a time of trip as a percentage of the
n
(VT).
n
(VT)
(VT).
(VT). If element 59P-2 is not based on negative
n
, dashes are shown on the LCD and "999"
2
(VT). If element 27P-2 is not based on positive
n
, dashes are shown on the LCD and "999"
1
(VT).
1MRS755972
during the last fault
n