ABB REU 610 Technical Reference Manual page 74

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

REU 610
Table 5.1.15.2.-14Fault record (Continued)
Address
Signal name
611
Residual voltage U
612
Maximum pick-up phase-to-phase voltage
613
Minimum pick-up phase-to-phase voltage
614
Maximum pick-up negative phase-sequence voltage
U
2
615
Minimum pick-up positive phase-sequence voltage
U
1
616
Maximum residual voltage U
617
Pickup duration of element 59P-1
618
Pickup duration of element 59P-2
619
Pickup duration of element 27P-1
620
Pickup duration of element 27P-2
621
Pickup duration of element 59N-1
622
Pickup duration of element 59N-2
623
Pickup duration of external trip
a)
Readable and writeable register.
b)
If not in use, the value 655 is returned.
Table 5.1.15.2.-15Event record
Address
Signal name
671
Latest selection code
672
Sequence number
673
Unread records left
674
Time stamp of the event, date
675
Time stamp of the event, date and time
676
Time stamp of the event, time
677
Time stamp of the event, time
678
Event data
679
74
Voltage Relay
Technical Reference Manual - ANSI Version
n
n
Structure 3
This structure contains Modbus event records. Refer to Event records earlier
in this section for the reading method.
a)
Range
Comment
0...200
0...200% U
n
0...200
0...2 × U
(VT)
n
0...200
0...2 × U
(VT)
n
0...200
0...2 × U
(VT)
n
0...200
0...2 × U
(VT)
n
0...200
0...200% U
n
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
0...100
0...100%
Range
Comment
1...3
1 = read oldest unread
record
2 = read oldest stored record
3 = clear Modbus event
buffer
-1...-99
-1...-99 = move to the nth
newest record
1...255
0...99
2 bytes: YY.MM
2 bytes: DD.HH
2 bytes: MM.SS
0...999
0...999 ms
See Table 5.1.15.2.-16 for
Modbus DI-point events and
Table 5.1.15.2.-17 for
informative events
1MRS755972
(VT)
b)
b)
(VT)