ABB REU 610 Technical Reference Manual page 99

Voltage relay
Hide thumbs Also See for REU 610:
Table of Contents

Advertisement

1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
Table footnotes from previous page
a)
When the value is 1, the digital input is energized.
b)
If the optional I/O module has not been installed, a dash is shown on the LCD and "9" when the
parameter is read via the SPA bus.
Each protection element has its internal output signal. These signals can be
read with parameters O1...O15 and the recorded functions with parameters
O61...O75. The state of the output contacts can be read or changed with
parameters O41...O49 and the recorded functions read with parameters
O101...O109.
Table 5.1.17.-9 Output signals
Status of the
State of element
protection
(R), channel 0
elements
Pickupof element
59P-1
Trip of element 59P-
1
Pickupof element
59P-2 or 47
Trip of element 59P-
2 or 47
Pickupof element
27P-1
Trip of element 27P-
1
Pickupof element
27P-2 or 27D
Trip of element 27P-
2 or 27D
Pickupof element
59N-1
Trip of element 59N-
1
Pickupof element
59N-2
Trip of element 59N-
2
External trip
Trip lockout
CBFAIL trip
Recorded
functions (R),
channel 0
O1
O61
O2
O62
O3
O63
O4
O64
O5
O65
O6
O66
O7
O67
O8
O68
O9
O69
O10
O70
O11
O71
O12
O72
O13
O73
O14
O74
O15
O75
REU 610
Value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
99