Table 7.-2
Setting group 2
Variable
Pickup value of element 59P-
1
Operate time of element
59P-1
IDMT operation mode setting
for element 59P-1
IDMT time dial 59P-1 TD
Resetting time of element
59P-1
Drop-off/pick-up ratio 59P-1
D/P
U
/U
mode setting of
1
2
elements 59P-2 and 27P-2
Pickup value of element 59P-
2
Pickup value of element 47
Operate time of element
59P-2
IDMT operation mode setting
for element 59P-2
IDMT time dial 59P-2 TD
Pickup value of element 27P-
1
Operate time of element
27P-1
IDMT operation mode setting
for element 27P-1
IDMT time dial 27P-1
Resetting time of element
27P-1
Drop-off/pick-up ratio D/P<
Pickup value of element 27P-
2
Pickup value of element 27D
Operate time of element
27P-2
IDMT operation mode setting
for element 27P-2
IDMT time dial 27P-2 TD
Pickup value of element
59N-1
Group/
Setting range
Channel 2
(R, P)
2S1
0.6...1.4 × U
n
(VT)
2S2
0.06...600 s
2S3
0...2
2S4
0.05...2.00
2S5
0.07...60.0 s
2S6
0.95...0.99
2S7
0...2
2S8
0.80...1.60 × U
(VT)
2S9
0.05...1.00 × U
(VT)
2S10
0.05...600 s
2S11
0...2
2S12
0.05...2.00
2S13
0.20...1.20 × U
(VT)
2S14
0.10...600 s
2S15
0...1
2S16
0.10...2.00
2S17
0.07...60.0 s
2S18
1.01...1.05
2S19
0.20...1.20 × U
(VT)
2S20
0.20...1.20 × U
(VT)
2S21
0.10...600 s
2S22
0...1
2S23
0.10...2.00
2S24
2.0...80.0% U
(VT)
REU 610
Default
Custo-
setting
mer's
setting
1.2 × U
n
(VT)
0.06 s
0
0.05
0.07 s
0.97
0
1.20× U
n
n
(VT)
0.05 × U
n
n
(VT)
0.05 s
0
0.05
0.20 × U
n
n
(VT)
0.10 s
0
0.10
0.07 s
1.03
0.20 × U
n
n
(VT)
0.20 × U
n
n
(VT)
0.10 s
0
0.10
2.0% U
n
n
(VT)